We provide a complete line of general products and services to assist you with exit and emergency lighting, fire hoses, signs, flammable liquid cabinets and other safety related products.
Exit/Emergency Lighting Inspection
Monthly
- Ensure the emergency lighting equipment is in its designated place.
- Inspect the housing for physical damage.
- Push test switch for 30 seconds.
- Verify lamps are illuminated and aimed in the correct direction.
- Maintain the monthly log for inspection by the authority having jurisdiction (AHJ).
Annually
- Conduct a thorough examination of the unit.
- Conduct an operational test of the battery and lighting system for the required 90 minutes.
- Check condition and voltage of the battery and verify manufacture date.
- Check AC/DC lamps or bulbs for damage and proper operation.
- Verify charging circuit is operational and working properly.
- Apply emergency lighting test label to each light upon completion.